Wire safely.
Electrical wire gauge (AWG) for any amp load and run length. Accounts for voltage drop so your circuit stays within code.
How we calculated this
The calculator steps through standard AWG wire gauges from smallest to largest, checking two constraints for each: ampacity (does the wire handle the current without overheating?) and voltage drop (does the voltage at the load stay within the allowed percentage of the source voltage?). The smallest wire that meets both constraints is the recommendation.
Ampacity values come from NEC Table 310.16, the industry standard for conductor capacity in typical residential conditions (60-75°C insulation, up to 3 current-carrying conductors in a raceway, 30°C ambient). For unusual installations (conduit fill above 3 wires, high ambient temperature, direct burial), derating factors apply: consult NEC or an electrician.
Voltage drop is calculated using the standard formula VD = 2 × I × R × L / 1000, where 2 accounts for the round-trip (current flows out on one conductor and back on another), I is amperage, R is resistance per 1000 ft, and L is the one-way distance. The 3% branch / 5% feeder limit in the NEC is a recommendation, not a code requirement, but exceeding it causes poor appliance performance and wasted energy.
For long runs (over 100 ft at 15-20A), voltage drop usually drives the wire size up from what ampacity alone would suggest. For short runs at high current (under 30 ft at 50A+), ampacity is the binding constraint. The calculator tells you which one drove the choice.
Aluminum wire has lower ampacity than copper for the same AWG (about 80% of copper's rating) and higher resistance (about 60% more). For long runs, aluminum requires a larger gauge to achieve the same voltage drop. Aluminum is common for service entrance and subpanel feeders; copper is standard for branch circuits and where terminals aren't rated for aluminum.
Two rules decide the wire, and only one of them is on the label
Wire sizing answers two separate questions, and skipping the second is how a legal circuit ends up with dim lights and a hot motor. First, ampacity: can the conductor carry the current without overheating? That is a table lookup, and for ordinary house wiring it is short enough to memorize. 14 AWG copper is 15 amps, 12 AWG is 20, 10 AWG is 30, 8 AWG is 40, 6 AWG is 55. Second, voltage drop: over the distance you are running, does enough voltage actually arrive? A 12 AWG circuit is fine at 30 feet and marginal at 80, even though the table never changes.
The calculator above answers both at once and returns the larger of the two answers, which is the one that governs. This page covers the full ampacity chart for copper and aluminum, the 60 degree column rule that catches nearly every DIY mistake, the wire sizes for common appliances and services, and how far each gauge really runs.
How we calculated these numbers▾
Ampacity values follow NEC Table 310.16 at the 60 and 75 degree C columns. Branch circuits using NM-B cable are limited to the 60 degree column by NEC 334.80 regardless of the cable's printed rating. The 15, 20, and 30 amp ceilings on 14, 12, and 10 AWG copper come from NEC 240.4(D), which caps overcurrent protection on small conductors below their table ampacity. Voltage drop figures use the 3 percent branch circuit target from the informational note to NEC 210.19(A) and standard conductor resistance. Local amendments and inspector judgment override all of it.
The wire size chart
Copper | Aluminum | Typical load | |
|---|---|---|---|
| 15 A | 14 AWG | not used | Lighting, bedroom outlets |
| 20 A | 12 AWG | not used | Kitchen, bath, laundry, garage |
| 30 A | 10 AWG | 8 AWG | Dryer, water heater, window AC |
| 40 A | 8 AWG | 6 AWG | Electric range, 32 A EV charger |
| 50 A | 6 AWG | 4 AWG | Range, 40 A EV charger, small subpanel |
| 60 A | 6 AWG | 4 AWG | Subpanel, shop feeder |
| 100 A | 4 AWG | 2 AWG | Subpanel or small service |
| 125 A | 2 AWG | 1/0 AWG | Service on a smaller or older house |
| 150 A | 1 AWG | 2/0 AWG | Service or large subpanel |
| 200 A | 2/0 AWG | 4/0 AWG | Standard modern house service |
Copper and aluminum sizes for common breaker ratings. Aluminum runs roughly two gauge sizes larger for the same current, which is why service entrance cable is usually aluminum: it is cheaper per amp delivered.
The rows people search for, stated plainly. A 20 amp circuit takes 12 AWG copper, never 14, and this is the single most common wiring error in DIY work because 14 AWG is cheaper and easier to bend. For 50 amp wire size, use 6 AWG copper or 4 AWG aluminum. The 100 amp service wire size is 4 AWG copper or 2 AWG aluminum, and 125 amp service, common on houses upgraded in the 1980s, takes 2 AWG copper or 1/0 aluminum. The 200 amp service wire size is 2/0 copper or 4/0 aluminum; service entrance conductors for dwellings get a small allowance under NEC 310.12 that lets them run slightly smaller than a general feeder of the same rating, which is why the service table looks generous next to the subpanel numbers.
Why the cable says 90 C and you still use 60
Every roll of NM-B cable is printed with a 90 degree C rating, and the 90 degree column of Table 310.16 shows 12 AWG at 30 amps. Both are true, and neither lets you put 12 AWG on a 30 amp breaker. NEC 334.80 requires NM cable to be sized from the 60 degree column, and the reason is the hardware at each end: breakers, receptacles, and panel lugs are listed for 60 or 75 degree terminations, so the weakest link governs the whole circuit. The 90 degree rating exists for derating math, where you start from the higher number and subtract for bundling or ambient heat, but the final answer can never exceed the 60 degree value.
Two derating cases come up in real houses. Bundling: once more than three current-carrying conductors share a conduit or pass bundled through more than 24 inches of framing, ampacity drops, 80 percent for four to six conductors and 70 percent for seven to nine. Ambient heat: an attic in Phoenix can run above 100 degrees F, and conductors up there lose ampacity accordingly, which is why long attic runs sometimes need the next size up even though the length alone would not demand it.
Voltage drop and how far a circuit really runs
Voltage drop is not a code violation. NEC 210.19 puts the 3 percent branch circuit and 5 percent total targets in an informational note, which means recommended rather than required. It is still worth respecting, because the symptoms are real: motors draw more current at lower voltage and run hotter, incandescent and some LED fixtures dim visibly, and heating elements lose output roughly with the square of the voltage. A detached garage 120 feet away on 12 AWG at 120 volts is the classic complaint, and the fix at the design stage costs one wire size.
Two structural facts make long runs easier. Doubling voltage roughly doubles the distance you can run at the same drop, which is why a detached shop is fed at 240 volts with a subpanel rather than by extending 120 volt circuits. And drop is proportional to current, so a lightly loaded long run is fine while a fully loaded one is not. If the load is a continuous one, such as an EV charger or electric heat, the 125 percent continuous load rule in NEC 210.19 already pushes the conductor up before voltage drop enters the picture.
Low-voltage DC: solar, automotive, and speaker wire
Wire sizing for 12, 24, and 48 volt DC follows the same two rules, but the balance between them flips completely. At 12 volts, voltage drop governs almost every run, because a 3 percent budget on 12 volts is only 0.36 volts. A 20 amp accessory circuit that would take 12 AWG in a house needs 10 AWG at 10 feet and 6 AWG at 25 feet in a 12 volt system. This is why marine and RV wiring looks absurdly oversized to anyone used to household work: it is not overbuilt, it is correctly built for the voltage.
Three practical notes for DC work. Stranded wire, not solid, for anything that vibrates or flexes, which is every vehicle and most boats. Solar arrays are usually wired at higher DC voltage specifically to escape this problem, which is why a 48 volt battery bank moves the same power through a quarter of the copper a 12 volt bank needs. And speaker wire is the one case where the 3 percent rule is the wrong target: speaker runs are sized against the load impedance, and the common guidance is to keep total wire resistance under about 5 percent of the speaker impedance, which for an 8 ohm speaker means 16 AWG covers most residential runs and 14 AWG handles long ones. Set the voltage selector on the calculator above to 12, 24, or 48 volts and it applies the DC math directly.
Aluminum: fine on feeders, a problem in old branch circuits
Modern aluminum building wire, the AA-8000 series alloy, is a legitimate and common choice for service entrances and large feeders. It is meaningfully cheaper per amp, it is what most utilities run to the meter, and 4/0 aluminum feeding a 200 amp panel is completely ordinary. It needs the right treatment: connectors listed AL or CU-AL, antioxidant compound on the terminations, and torque set with a torque screwdriver rather than by feel, because aluminum creeps under pressure in a way copper does not.
The bad reputation comes from a different product. Houses wired between roughly 1965 and 1973 used solid aluminum in 15 and 20 amp branch circuits, and the CPSC found those connections far more likely to reach fire hazard conditions than copper. If you open a receptacle box and find solid aluminum branch wiring, that is an evaluation-by-an-electrician situation and not a DIY repair; the accepted repairs are specific listed connectors or a rewire, and simply replacing devices does not fix it.
A Level 2 EV charger in a detached garage, 85 feet of run from the main panel. The charger is a 48 amp unit, which is a continuous load, so NEC 210.19 requires the circuit at 125 percent: 48 x 1.25 = 60 amps. That sets a 60 amp breaker and 6 AWG copper from the ampacity table.
Now the distance check. Six AWG copper at 60 amps over 85 feet at 240 volts drops about 2.7 percent, just inside the 3 percent target, so 6 AWG holds on both counts. Had the run been 120 feet, the drop would pass 3.8 percent and the sensible answer is 4 AWG, about $1.40 more per foot and roughly $170 on this job. In an Austin garage that hits 110 degrees F in August, the ambient derating is worth checking with the electrician too, since a hot garage is exactly where the margin disappears. The permit and inspection are required either way.
Composite illustration based on typical project dimensions, regional contractor pricing, and 2026 material costs. Not a specific real project.
Where wire sizing goes wrong
Using 14 AWG on a 20 amp circuit. The most common one, and the most consequential. The breaker protects the wire, not the device; a 20 amp breaker will happily let 18 amps flow through a conductor rated for 15 until the insulation fails somewhere inside a wall.
Upsizing the breaker instead of the wire. When a breaker trips repeatedly, the breaker is doing its job. Replacing a 15 amp breaker with a 20 to stop the nuisance leaves 14 AWG protected at 20 amps, which is the textbook cause of an electrical fire.
Ignoring the continuous load rule. Anything running three hours or more without a break, such as EV charging, electric heat, or shop lighting, is sized at 125 percent of its load. A 40 amp charger is a 50 amp circuit, not a 40 amp one.
Forgetting the neutral and ground. A 240 volt appliance circuit may need a neutral depending on the appliance, and the equipment ground sizing comes from its own table, NEC 250.122, not from the ampacity table. Buying 6/2 cable when the range needs 6/3 is a return trip.
Circuits are part of a larger plan
Wire sizing usually shows up inside a bigger job. A new EV or shop circuit often accompanies a solar calculator estimate on the same panel, portable tools raise the separate question the extension cord calculator answers, and sizing the cooling load that a new circuit will serve runs through the BTU calculator.
Run your amps, volts, and distance through the calculator above, take the larger of the two answers, and bring that number to the electrician. Being right about the wire is the cheapest part of any electrical project.
Frequently asked
What gauge wire do I need for a 20 amp circuit?
For a typical 20 amp residential circuit with a run under 50 feet, use 12 AWG copper (the NEC minimum for 20 amps). For runs over 100 feet, voltage drop may require stepping up to 10 AWG. Use the calculator above with your specific distance.
What's the difference between ampacity and voltage drop?
Ampacity is the maximum current a wire can carry without overheating: it's a safety limit. Voltage drop is the power lost to resistance over distance: it's a performance limit (poor appliance operation, wasted energy). Both must be respected: a wire must have ampacity for the current AND low enough voltage drop for the distance.
Can I use aluminum wire for branch circuits?
Modern aluminum alloys are safe for service entrances and subpanel feeders. For branch circuits (outlets, lights, appliances), copper is strongly preferred: older aluminum in branch circuits is a known fire hazard. If you're installing new, use copper. If you have existing aluminum branch wiring, have it inspected.
What happens if the wire is too small?
Undersized wire overheats under load, which melts insulation and causes fires. The breaker protects against short circuits but not against a wire slightly too small for the continuous load, a 20A breaker on 14 AWG wire will allow the wire to overheat even though the breaker isn't tripping. Always match wire size to breaker size at minimum.
Do long runs really need bigger wire?
Yes. A 100-foot run of 14 AWG at 15 amps drops 3.7% voltage: above the 3% recommendation. At 200 feet it's 7.4%, which will cause motors and LEDs to perform poorly. For long runs, always run the voltage drop calculation: ampacity alone isn't enough.
What about DC wiring for solar and automotive?
Same formulas apply but voltage drop matters more because DC systems often run at lower voltages (12/24/48V). A 3% drop on a 12V system is only 0.36V, not much headroom. For DC solar and automotive, many installers target 2% max drop, which means even larger wire. The calculator's 2% option covers this case.
Is this calculator NEC-compliant?
The ampacity values match NEC 310.16 (60-75°C copper and aluminum at 30°C ambient, 3-conductor raceway). Voltage drop calculations use standard DC resistance from NEC Table 8. For unusual conditions (high ambient temperature, conduit fill > 3 conductors, direct burial), additional derating applies that the calculator doesn't model. For code-critical installations, have an electrician verify.
Should I oversize wire?
For long runs or continuous loads (EV chargers, AC condensers), yes, one gauge larger than the minimum provides headroom for future load increases and reduces voltage drop. For standard outlets and lighting in short runs, minimum code is fine. The cost difference between sizes is modest, so erring larger is cheap insurance.
Sources
- NEC (NFPA 70) Table 310.16: Conductor Ampacity - The ampacity values for copper and aluminum at the 60, 75, and 90 degree columns
- NEC 240.4(D): Small Conductor Overcurrent Protection - Caps 14, 12, and 10 AWG copper at 15, 20, and 30 amps regardless of table ampacity
- NEC 334.80: Ampacity of Nonmetallic-Sheathed Cable - Requires NM-B cable to be sized from the 60 degree column despite its 90 degree marking
- NEC 310.12: Dwelling Unit Services and Feeders - The allowance that lets residential service conductors run smaller than general feeders
- CPSC: Repairing Aluminum Wiring - The federal safety guidance on 1960s and 70s solid aluminum branch circuits
Was this calculator helpful?